Message structure for execute_local_pccc – Rockwell Automation 20-750-DNET PowerFlex DeviceNet Option Module User Manual
Page 104

104
Rockwell Automation Publication 750COM-UM002B-EN-P - October 2012
Appendix C
DeviceNet Objects
Message Structure for Execute_Local_PCCC
The option module supports the following PCCC command types:
For more information regarding PCCC commands, see the DF1 Protocol and
Command Set Manual, publication
.
Request
Response
Name
Data Type
Description
Name
Data Type
Description
CMD
USINT
Command byte
CMD
USINT
Command byte
STS
USINT
0
STS
USINT
Status byte
TNSW
UINT
Transport word
TNSW
UINT
Transport word. Same value as the request.
FNC
USINT
Function code; not used for all CMDs
EXT_STS
USINT
Extended Status; not used for all CMDs
PCCC_params
ARRAY of USINT
CMD/FNC specific parameters
PCCC_results
ARRAY of USINT
CMD/FNC specific result data
CMD
FNC
Description
0x06
0x03
Identify host and some status
0x0F
0x67
PLC-5 typed write
0x0F
0x68
PLC-5 typed read
0x0F
0x95
Encapsulate other protocol
0x0F
0xA2
SLC 500 protected typed read with 3 address fields
0x0F
0xAA
SLC 500 protected typed write with 3 address fields
0x0F
0x00
Word range read
0x0F
0x01
Word range write