92

Rockwell Automation Publication 750COM-UM002B-EN-P - October 2012

Appendix B

Option Module Parameters

About Parameter Numbers

Each parameter set is independently and consecutively numbered.

How Parameters Are
Organized

The

Device parameters and Host parameters are separately displayed in a

Numbered List

view order.

Device Parameters

Configuration Tool

Numbering Scheme

• HIM
• Connected Components Workbench software
• DriveExplorer software
• DriveExecutive software

The Device parameters and Host parameters begin with parameter
01. For example, Device Parameter 01 - [Port Number] and
Host Parameter 01 - [Net to Drv DL 01] are parameter 01 as
indicated by this manual.

• Explicit Messaging

See

Chapter 6

, Using Explicit Messaging and

Appendix C

,

DeviceNet Objects for details.

Parameter

No.

Name and Description

Details

01

[Port Number]
Displays the drive port into which the option module is installed.
Typically, this will be Port 4, 5 or 6.

Minimum:

0

Maximum:

7

Type:

Read Only

02

[DLs From Net Cfg]
Sets the number of contiguous controller-to-drive Datalinks
(additional parameters) that are included in the network I/O
connection. Logic Command and Reference are always included
in the I/O connection. This parameter controls how many of the
contiguous Host [DL From Net xx] parameters (16 maximum)
are active. For example, if this parameter value is set to ‘5’, then
Host Parameters 01 - [DL From Net 01] through 05 - [DL
From Net 05]
will be updated.

Default:

0

Minimum:

0

Maximum:

16

Type:

Read/Write

Reset Required:

Yes

03

[DLs From Net Act]
Displays the value of Device Parameter 02 - [DLs From Net
Cfg]
at the time the drive was reset. This is the number of actual
contiguous controller-to-drive Datalinks that the drive is
expecting.

Minimum:

0

Maximum:

16

Type:

Read Only

04

[DLs To Net Cfg]
Sets the number of contiguous drive-to-controller Datalinks
(additional parameters) that are included in the network I/O
connection. Logic Status and Feedback are always included in the
I/O connection. This parameter controls how many of the
contiguous Host [DL To Net xx] parameters (16 maximum) are
active. For example, if this parameter value is set to ‘5’, then Host
Parameters 17 - [DL To Net 01]
through 21 - [DL To Net 05]
will be updated.

Default:

0

Minimum:

0

Maximum:

16

Type:

Read/Write

Reset Required:

Yes

05

[DLs To Net Act]
Displays the value of Device Parameter 04 - [DLs To Net Cfg] at
the time the drive was reset. This is the number of actual
contiguous drive-to-controller Datalinks that the controller is
expecting.

Minimum:

0

Maximum:

16

Type:

Read Only

06

[Net Addr Src]
Displays the source from which the option module’s node address
is taken. This will be either the Node Address switches (

Figure 1

on page 18

) or the value of Device Parameter 07- [Net Addr

Cfg].

Values:

0 = Switches
1 = Parameters

Type:

Read Only