Bulletin 283 parameters – Rockwell Automation 283A ArmorStart with ArmorPoint Backplane - Getting Started User Manual

Page 25

Advertising
background image

Publication 283A-QS001C-EN-P - July 2006

25

Bulletin 283 Parameters

Table 7

Starter Display and Parameter Settings

Table 8

FLA Setting Ranges and Default Values (with indicated setting precision)

Parameter

Name String

Path (hex)

Min

Max

Dflt

Type

Value

SMC Display

101

Phase A Current

002C – 01 – 08

0

32767

INT

xxx.x Amps

102

Phase B Current

002C – 01 – 09

0

32767

INT

xxx.x Amps

103

Phase C Current

002C – 01 – 0A

0

32767

INT

xxx.x Amps

104

Average Current

002C – 01 – 05

0

32767

INT

xxx.x Amps

105

% Therm Utilized

002C – 01 – 07

0

100

USINT

xxx %

SMC Settings

106

FLA Setting

002C – 01 – 03

See Table 8 below

Min I

INT

xxx.x Amps

107

OL Trip Class

002C – 01 – 04

0

3

1

BYTE

1 = 10

108

OL Reset Level

0029 – 01 – 131

0

100

75

BYTE

xxx %

109

Start Time

000F - 06D - 01

1

45

10

USINT

sec

110

Start Mode

000F - 06E - 01

0

1

0

BOOL

0 = Current Limit

1 = Soft Start

111

Current Limit

000F - 06 - 01

150

600

350

UINT

xxx % FLA

Display multiplier of 10.

SMC is looking for values

between 15 and 60.

112

Initial Torque

000F - 070 - 01

0

90

60

USINT

% LRT

113

Soft Stop Time

000F - 071 - 01

0

90

0

USINT

sec

114

Kick Start

000F - 072 - 01

0.0

1.5

0.0

USINT

sec

115

SCR Temp Reset Mode

000F - 073 - 01

0

1

0

BOOL

0 = Manual

1 = Auto Reset

116

Phase Rotation

000F - 074 - 01

0

1

0

BOOL

0 = Disable

1 = Enable

FLA Current Range (A)

Default Value

Minimum Value

Maximum Value

1.1

3.0

1.1

3.0

5.5

3.0

5.3

7.6

5.3

6.3

16.0

6.3