ArmorConnect Cable Ratings

The ArmorConnect Power Media cables are rated per UL Type TC
600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or
STOOW 105 °C 600V - CSA STOOW 600V FT2. For additional
information regarding ArmorConnect Power Media see the ArmorStart
User Manual.

Branch Circuit Protection Requirements for ArmorConnect™
Three-Phase Power Media

When using ArmorConnect Three-Phase Power Media, only fuses can be
used for the motor branch circuit protective device, for the group motor
installations. The recommended fuse types are the following: Class CC, T,
or J type fuses. For additional information, see the ArmorStart User
Manual.

Terminal Designations

Description

Color Code

A1 (+)

Control Power Input

Blue

A2 (-)

Control Power Common

Black

PE

Ground

Green/Yellow

1/L1

Line Power - Phase A

Black

2/L2

Line Power - Phase B

White

3/L3

Line Power - Phase C

Red