Quick Start for Experienced Users

Procedures

Step

Action

For Further Information

Refer to…

1.

Review Attention statements in the Preface.

2.

Ensure that power to the 160 Drive has been removed.

160 Drive

User Manual

3.

Verify that the 160 Drive is correctly installed and
wired. Stop Input (TB3-7, TB3-8) must be jumpered
together to start drive.

160 Drive

User Manual

4.

Configure the 160 Drive for the IB1 Module so the drive
can accept control logic and speed reference via the
network. *

Chapter 5

(Parameters)

Set P46 - [Input Mode] to a value of “2” or “6” as described
in Table 6.A. This will configure the drive to accept the logic
commands from the network.

Note: If the value has to be changed, set P56 - [Reset
Functions]
to “2” or reboot the drive.

Set P59 - [Frequency Select] to “1.” This will configure the
drive to accept speed commands from the network.

Set P66 - [RPM Scaling] for the RPM/Hz Scaling factor.
This allows theNetwork Reference to be in RPM.

5.

Remove Program Keypad Module or Ready/Fault
Indicating Panel from the drive.*

Chapter 3

(Installation)

6.

Install the IB1 Module.

Chapter 3

(Installation)

7.

Connect communication cable.

Chapter 3

(Installation)

8.

Power up the drive and the network.

Chapter 3

(Installation)

9.

Check for proper operation.

* Parameter setting might also be done via the

Keypad Module prior to removal