InterBus Parameter Descriptions and Data Protocol

5–5

Parameter Access

Parameter access is established by object indices and parameter
related sub-indices to be sent via the PCP telegram.

Table 5.E

Parameter attributes

Each parameter is described by an attribute to be read according to
table 5.F. The attribute consists of one word with 2 bytes which are
defined as follows:

High Byte stores the Unit (scaling) according to the table 5.G,

Low Byte stores the parameter number.

Table 5.F

Parameter Access Fault Codes

("Additional Error Codes")

The error messages listed in the table 5.G indicated problems when
attempting to access parameters via PCP.

The drive will NOT fault but indicate to the user that a specific
parameter access failed.

Table 5.G

Parameter

Type

Parameter

Numbers

Index

Sub-Index (decimal)

Display

P01 – P20,

P30 – P84

0x5FF0

1 to 99(1-20, 30-84) Read

Program

P30 – P84

0x5FF1

1 – 86 (84) Read Parameter Default

Program

P30 – P84

0x5FF2

1 – 86 (84) Read Parameter Low Limit

Program

P30 – P84

0x5FF3

1 – 86 (84) Read Parameter High Limit

Program

P30 – P84

0x5FF4

1 – 86 (84) Read Parameter Attribute

Program

P30 – P84

0x5FF9

30 – 86 (84) Write

Fault Code

0x603F

Active Fault according to Table 8B

High Byte

Units

0

Decimal

1

1

Decimal

0.1

2

Decimal

0.01

3

Hexadecimal

1

4

Binary

1

5

Decimal (signed)

1

6

Decimal (signed)

0.1

7

Decimal (signed)

0.01

Error Code

Error

1

Parameter size is too small (e.g. byte instead of word)

4

Parameter value is out of limits

10

Parameter write attempt while drive is running

11

Parameter number too small

12

Parameter size is too large (e.g. 3 bytes instead of two bytes)

20

Parameter number not valid

22

Parameter number is too high

30

No valid response from drive