Troubleshooting

Communication Status LEDs

In case no LED is on, check the options connected to the SSC160.

The four Communication Status LEDs provide status information on
module operations. Table 8.A shows how to use the LED to detect and
correct common operating problems.

Table 8.A
Communication Status LEDs Indications

FLT LED

When the FLT LED is red, a drive fault is present.

Table 8.B
InterBus Faults (DRIVECOM 20

)

in Object 603F

Name
(Function)

State

What It Means:

What To Do:

RC
(Remote Bus
Check)

Off

No power, processor reset,
InterBus reset or network link to
predecessor in line interrupted

Check Power Supply, Network
Cable and InterBus Master
operation.

yellow

Input cable connection o.k.

No action required.

BA
(Bus Active)

Off

Bus inactive

Check InterBus Master setup.

green

Bus Active / Data exchange

No action required.

TR (Transmit/
Receive)

Off

No PCP Communication

If PCP operation is desired, check
IB Master setup (initiate PCP).

green

PCP Communication active

No action required.

RD
(Remote Bus
Disable)

Off

Outgoing InterBus enabled

No action required.

red

InterBus Reset or outgoing Bus
disable

No action required on last device
in line (emty top plug). Otherwise
check cabling and reset Master.

Fault No.
[Hex]

Fault Name

Fault Code
SSC160
[Dec]

0

no fault

0

1000

General Malfunction

nn

2200

Internal Current

13

2300

Current on Device Output Side

12

2320

Current on Device Output Side: Short Circuit/ Earth Leakage

46

2331

Current on Device Output Side: Earth Leakage Phase U

38

2332

Current on Device Output Side: Earth Leakage Phase V

39

2333

Current on Device Output Side: Earth Leakage Phase W

40

2341

Current on Device Output Side: Short Circuit Phases U-V

41

2342

Current on Device Output Side: Short Circuit Phases V-W

42

2343

Current on Device Output Side: Short Circuit Phases W-U

43

3210

Internal Over Voltage

5

3221

Internal Under Voltage No. 1

3

3222

Internal Under Voltage No. 2

4

4210

Excess Temperature Device

8

4310

Excess Temperature Drive

20

5000

Model of drive not valid

5300

Device Hardware: Operating Unit

11

5310

Device Hardware: Data Storage RAM

5320

Device Hardware: Data Storage EPROM

6100

Device: Internal Software

32

6200

Device: User Software

33

6320

Device Software/ Data Record: Parameter Error

48

7500

IBS fatal protocol error