Using an EMI filter with any drive rating, may result in relatively high 
ground leakage currents. Therefore, the filter must only be used in 
installations and solidly grounded (bonded) to the building power 
distribution ground. Grounding must not rely on flexible cables and 
should not include any form of plug or socket that would permit 
inadvertent disconnection. Some local codes may require redundant 
ground connections. The integrity of all connections should be 
periodically checked.
Grounding
Connect a grounding conductor to the terminal provided as standard on each 
ArmorStart Distributed Motor Controller. Refer to Table 2 for grounding 
provision location. There is also an externally available ground terminal. 
Refer to Figure 9.
LED Status Indication
The LED Status Indication provides 4 status LEDs and a Reset button. The 
LEDs provide status indication for the following:
•
POWER LED
The LED is illuminated solid green when control power is present and 
with the proper polarity
•
RUN LED
This LED is illuminated solid green when a start command and control 
power are present
•
NETWORK LED
This bi-color (red/green) LED indicates the status of the 
communication link
•
FAULT LED
Indicates Controller Fault (trip) condition
The “Reset Button” as a local trip reset.
Figure 6 LED Status Indication and Reset