Rockwell Automation 284G ArmorStart - Getting Started User Manual
Page 15

Publication 284G-QS001A-EN-P - December 2008
15
Table 6
Basic Program Group for Sensorless Vector Control
➊ Stop drive before changing this parameter.
➋ See Important below:
Parameter
Number
Parameter
Description
Display/
Options
Min./
Max.
Defaults
Settings
131
➊
Motor NP Volts
1 VAC
20/Drive Rated
Volts
Based on
Driving
Rating
132
➊
Motor NP Hz
1 Hz
15/400 Hz
60 Hz
133
Motor OL
Current
0.1 A
0.0/(Drive Rated
Amps x 2)
Based on
Driving
Rating
134
Minimum Freq.
0.1 Hz
0.0/400 Hz
0.0 Hz
135
➊
Maximum
Freq.
0.1 Hz
0.0/400 Hz
60 Hz
136
➊
Start Source
0 = Keypad ➋
1 = 3-Wire ➋
2 = 2-Wire
3 = 2-W Lvl Sens
4 = 2-W Hi Speed
5 = Comm Port
0/5
5
137
Stop Mode
0 = Ramp, CF
1 = Coast, CF
2 = DC Brake, CF
3 = DCBrkAuto, CF
4 = Ramp
5 = Coast
6 = DC Brake
7 = DC BrakeAuto
8 = Ramp + EM B, CF
9 = Ramp + EM Brk
0/9
9
138
Speed
Reference
0 = Drive Pot ➋
1 = InternalFreq
2 = 0…10V Input ➋
3 = 4…20 mA Input ➋
4 = Preset Freq
5 = Comm Port
6 = Stp Logic
7 = Anlg in Mult ➋
0/7
5
139
Accel Time 1
0.1 Secs
0.0/600.0 Secs
10.0 Secs
140
Decel Time 1
0.1 Secs
0.0/600.0 Secs
10.0 Secs
141
➊
Reset to
Default
0 = Ready/Idle
1 = FactoryRset
0/1
0
IMPORTANT
These drive parameters options will cause the
Bulletin 284G ArmorStart Distributed Motor Controller
to become disabled.