Rockwell Automation 284G ArmorStart - Getting Started User Manual

Page 20

Advertising
background image

20

Publication 284G-QS001A-EN-P - December 2008

Table 12 Fault Types, Descriptions, and Actions (Continued)

➊ See Table 10 for internal drive fault types.

No.

Fault

Type

Description

Action

F48

Params
Defaulted

2

The drive was commanded to write
default values to EEPROM.

1.

Clear the fault or cycle power to the drive.

2.

Program the drive parameters as needed.

F63

SW
OverCurrent

2

Programmed Parameter 198 [SW
Current Trip] has been exceeded.

Check load requirements and Parameter 198 (SW Current Trip) setting.

F64

Drive
Overload

2

Drive rating of 150% for 1 min. or
200% for 3 sec. has been
exceeded.

Reduce load or extend Accel Time.

F70

Power Unit

2

Failure has been detected in the
drive power section.

1.

Cycle power.

2.

Replace starter module if fault cannot be cleared.

F80

SVC Autotune

The autotune function was either
cancelled by the user or failed.

Restart procedure.

F81

Comm Loss

2

RS485 (DSI) port stopped
communicating.

1.

Turn off using Parameter 205 (Comm Loss Action).

2.

Replace starter module if fault cannot be cleared.

F100

Parameter
Checksum

2

The checksum read from the board
does not match the checksum
calculated.

Set Parameter 141 (Reset To Defaults) to option 1 Reset Defaults.

F122

I/O Board Fail

2

Failure has been detected in the
drive control and I/O section.

1.

Cycle power.

2.

Replace starter module if fault cannot be cleared.