Wiring, Terminal designations for conduit entrance, Power, control, and ground wiring – Rockwell Automation 284G ArmorStart - Getting Started User Manual
Page 4

4
Publication 284G-QS001A-EN-P - December 2008
Wiring
Power, Control, and Ground Wiring
Table 1 provides the power, control, and ground wire capacity and the
tightening torque requirements. The power, control, and ground terminals
will accept a maximum of two wires per terminal.
Table 1
Power, Control, Ground Wire Size, and Torque Specifications
Terminal Designations for
Conduit Entrance
As shown in Figure 3, the ArmorStart Distributed Motor Controller contains
terminals for power, control, and ground wiring. Access can be gained by
removing the terminal access cover plate.
Figure 3 ArmorStart Power, Control, and Ground Terminals
Table 2
Power, Control, Safety Monitor, and Ground Terminal Designations
Terminals
Wire Size
Torque
Wire Strip Length
Three-phase
Power
and
Ground
Primary/Secondary
Terminal:
1.5…4.0 mm
2
(#16 …#10 AWG)
Primary Terminal:
10.8 lb•in. (1.2 N•m)
Secondary Terminal:
4.5 lb•in (0.5 N•m)
0.35 in. (9 mm)
Control and Power
1.0 mm
2
…4.0 mm
2
(#18…#10 AWG)
6.2 lb•in
(0.7 N•m)
0.35 in. (9 mm)
Terminal Designations
No. of Poles
Description
A1 (+)
2
Control Power Input
A2 (-)
2
Control Power Common
PE
2
Ground
1/L1
2
Line Power Phase A
3/L3
2
Line Power Phase B
5/L5
2
Line Power Phase C