Wiring, Terminal designations for conduit entrance, Power, control, and ground wiring – Rockwell Automation 284G ArmorStart - Getting Started User Manual

Page 4

Advertising
background image

4

Publication 284G-QS001A-EN-P - December 2008

Wiring

Power, Control, and Ground Wiring

Table 1 provides the power, control, and ground wire capacity and the
tightening torque requirements. The power, control, and ground terminals
will accept a maximum of two wires per terminal.

Table 1

Power, Control, Ground Wire Size, and Torque Specifications

Terminal Designations for
Conduit Entrance

As shown in Figure 3, the ArmorStart Distributed Motor Controller contains
terminals for power, control, and ground wiring. Access can be gained by
removing the terminal access cover plate.

Figure 3 ArmorStart Power, Control, and Ground Terminals

Table 2

Power, Control, Safety Monitor, and Ground Terminal Designations

Terminals

Wire Size

Torque

Wire Strip Length

Three-phase

Power

and

Ground

Primary/Secondary

Terminal:

1.5…4.0 mm

2

(#16 …#10 AWG)

Primary Terminal:

10.8 lb•in. (1.2 N•m)

Secondary Terminal:

4.5 lb•in (0.5 N•m)

0.35 in. (9 mm)

Control and Power

1.0 mm

2

…4.0 mm

2

(#18…#10 AWG)

6.2 lb•in

(0.7 N•m)

0.35 in. (9 mm)

Terminal Designations

No. of Poles

Description

A1 (+)

2

Control Power Input

A2 (-)

2

Control Power Common

PE

2

Ground

1/L1

2

Line Power Phase A

3/L3

2

Line Power Phase B

5/L5

2

Line Power Phase C