Response Time

The response time depends on the following parameters:
• Number of beams
• Beam coding
• Configuration of floating blanking
• Number of cascaded systems

How to determine the response time of the system:

➢ Read the response times of the individual systems (shown on

type label). Note whether the system is operated with or
without beam coding.

Note

If you are planning the application without actually having
any devices available, you may also determine the response
time using Table 26 on page 37 and Table 27 on page 38.
When determining the number of beams in Table 26, the
physical resolution is important. The physical resolution of
the light curtain does not change even if fixed or floating
blanking has been selected.

➢ Fill out the following table to determine the total response time.

Table 25: Determining the response time of a SafeShield safety light
curtain system

➢ Verify that the total response time determined is ≤108ms.

EN 61 496 does not permit response times exceeding 108ms. If
necessary, adjust the configuration.

Line Required Detail

Response Time

1

Host

ms

2

Guest 1

+

ms

3

Guest 2

+

ms

4

Only if floating
blanking is used:

Greatest response
time from lines
1 to 3: × 0.5 =

+

ms

Deduct 4ms here.

ms

5

If single guest is used, then add 8ms here. (If
no guest is used or two guests are used, do
not add anything here.)

+

ms

6

Total response time to be taken into
account (The total response time
must be

108ms!)

=

ms

Example

Calculating the response time for a cascaded system without beam
coding in which fields are configured with floating blanking:

Table 26: Number of beams depending on the protective field height and
the physical resolution

Line Required Detail

Response Time

1

Host: 750mm protective field height,
resolution 14mm

16ms

2

Guest 1: 300mm protective field height,
resolution 40mm

+

9ms

3

Guest 2: —

+

0ms

4

Only if floating
blanking is used:

Greatest response
time from lines
1 to 3: 16ms × 0.5 =

+

8ms

Deduct 4ms here.

4ms

5

If single guest is used, then add 8ms here. (If
no guest is used or two guests are used, do
not add anything here.)

+

8ms

6

Total response time to be taken into
account

=

37ms

Protective Field

Height [mm]

Number of Beams for Physical Resolution

14mm

30mm

300

40

15

450

60

23

600

80

30

750

100

38

900

120

45

1050

140

53

1200

160

60

1350

180

68

1500

200

75

1650

220

83

1800

240

90