Drive Wiring
This chapter describes how to wire the 1302 Drive including: input
wiring, control and signal wiring, output wiring, and grounding.
Input Power Wiring
Use the following steps to connect AC input power to the Drive:
Step 1. Verify that the AC input power to the Drive corresponds to
the drive’s nameplate voltage and frequency.
Step 2. Wire the AC input power leads by routing them according to
the type of enclosure. Sees Figures 4.1 and 4.2 and Table
3.B for recommended wire sizes.
!
ATTENTION: Do Not route signal and control wiring
with power wiring in the same conduit. This can cause
interference with Drive operation. Failure to observe
this precaution could result in erractic drive operation
or damage to, or destruction of, the equipment.
Step 3. Connect the AC input power leads to terminals R,S,T on the
power terminal strip.
Step 4. Tighten terminals R and S (single–phase input) or terminals
R,S,T (three–phase input) to the proper torque as shown in
Table 3.D.
Introduction