Technical Specifications
Table A.A - Service Conditions
AC Line Distribution Capacity
(Maximum)
ThreeĆphase 575ĂVAC, with 30,000Ăamps symmetrical
fault current capacity
Control Method
AllĆdigital, pulseĆwidthĆmodulated (PWM)
Carrier Frequency
4ĂkHz, 6ĂkHz, or 8ĂkHz, software selectable
Displacement Power Factor
0.96
Line Frequency
50/60ĂHz (±5ĂHz)
Line Voltage Variation
ć10% to +10%
Line Dip RideThrough
500Ămilliseconds
Linearity
0.05 (Speed reference to output frequency)
LongĆterm Frequency Stability
0.01%
Minimum Frequency Range
0.5 ć 30ĂHz
Maximum Frequency Range
30 ć 240ĂHz
Maximum Load
150% for 1 minute (based on Drive nameplate rating)
Motor Lead Lengths
76Ămeters (250Ăfeet) total
(See table 3.7 for more
information)
Overcurrent Trip IET
200% rated Drive current
Table A.B - Dimensions
Enclosure
Height
Depth
Width
Weight
B
301.7Ămm (11.88")
160.1Ămm (6.30")
222.3Ămm (8.75")
5.4Ăkg (12 lb)
C
357.8Ămm (14.10")
158.2 mm (6.20")
278.1Ămm (10.9")
8.1Ăkg (18 lb)
Table A.C - Environmental Conditions
Operating Temperature
0° to +ā40°C (32° to 104°F) ć enclosed Drives
0° to +ā55°C (32° to 131°F) ć open chassis (cover removed)
Storage Temperature
ćāā40° to +65°C (ćāā40° to +149°F)
Humidity
5 to 95% (nonĆcondensing)
Altitude
Do not install the Drive above 1000Ămeters (3300Ăfeet) without
derating output power. For every 91.4Ămeters (300Ăfeet) above
1000Ămeters (3300Ăfeet) up to 3033Ămeters (10,000Ăfeet),
derate the output current by 1%. Above 3033Ămeters
(10,000Ăfeet), contact your local Allen-Bradley sales office for
assistance.