Technical Specifications

Table A.A - Service Conditions

AC Line Distribution Capacity

(Maximum)

ThreeĆphase 575ĂVAC, with 30,000Ăamps symmetrical

fault current capacity

Control Method

AllĆdigital, pulseĆwidthĆmodulated (PWM)

Carrier Frequency

4ĂkHz, 6ĂkHz, or 8ĂkHz, software selectable

Displacement Power Factor

0.96

Line Frequency

50/60ĂHz (±5ĂHz)

Line Voltage Variation

ć10% to +10%

Line Dip RideThrough

500Ămilliseconds

Linearity

0.05 (Speed reference to output frequency)

LongĆterm Frequency Stability

0.01%

Minimum Frequency Range

0.5 ć 30ĂHz

Maximum Frequency Range

30 ć 240ĂHz

Maximum Load

150% for 1 minute (based on Drive nameplate rating)

Motor Lead Lengths

76Ămeters (250Ăfeet) total

(See table 3.7 for more

information)

Overcurrent Trip IET

200% rated Drive current

Table A.B - Dimensions

Enclosure

Height

Depth

Width

Weight

B

301.7Ămm (11.88")

160.1Ămm (6.30")

222.3Ămm (8.75")

5.4Ăkg (12 lb)

C

357.8Ămm (14.10")

158.2 mm (6.20")

278.1Ămm (10.9")

8.1Ăkg (18 lb)

Table A.C - Environmental Conditions

Operating Temperature

0° to +ā40°C (32° to 104°F) ć enclosed Drives
0° to +ā55°C (32° to 131°F) ć open chassis (cover removed)

Storage Temperature

ćāā40° to +65°C (ćāā40° to +149°F)

Humidity

5 to 95% (nonĆcondensing)

Altitude

Do not install the Drive above 1000Ămeters (3300Ăfeet) without

derating output power. For every 91.4Ămeters (300Ăfeet) above

1000Ămeters (3300Ăfeet) up to 3033Ămeters (10,000Ăfeet),

derate the output current by 1%. Above 3033Ămeters

(10,000Ăfeet), contact your local Allen-Bradley sales office for

assistance.