Page 60: Press the, 8–2 programming

Advertising
background image

8–2

Programming

Publication 1302-5.0 — January, 1998

Step 5 .Press the

or

key to change the value.

Mode
Enter

START

Forward
Reverse

STOP

RESET

RPM

%Load

Volts

Remote

RUN

Program

Forward

Reverse

Note that if programming has been disabled in parameter F-20
(Password Lockout Enable), the value will not change. Refer to
Chapter 8, Ensuring Program Security, for more information.

Step 6.

Press the

Mode
Enter

key to save the changed value.

Mode
Enter

START

Forward
Reverse

STOP

RESET

RPM

%Load

Volts

Remote

RUN

Program

Forward

Reverse

The parameter number is displayed again.

To display or change additional parameters, repeat steps 3
through 6.

To exit program mode, press the

Mode
Enter

key until a parameter

number or ERR is displayed; then press the

STOP

RESET

key.

Important: Parameter values and the keypad status (local or
remote) are retained through a line dip or power loss.

!

ATTENTION: It is your responsibility to determine how
to distribute the password. Allen–Bradley is not
responsible for unauthorized access violations within the
user’s organization. Failure to observe this precaution
could result in equipment damage or bodily injury.

Parameter values can be password-protected using parameter F-20
(Password Lockout Enable). When F-20 is set to ON, parameter
values can be displayed but cannot be modified from the keypad
unless the correct password is entered in F-20.

Note: The password is factory set to 257 and cannot be modified by
the user.

Program Security