Chapter – Rockwell Automation 1500 DeviceNet MV Controllers Installation Instructions User Manual
Page 13

Chapter
4
1500-IN057C-EN-P – June 2013
Linking DeviceNet Communication Cables
in Medium Voltage Controllers
Figure 4.1 – Joining the DeviceNet Trunk Line in Adjacent MV Sections
General
This section describes the recommended procedure for connecting
DeviceNet communication cables (trunk lines) in MV controllers. The
number of and type of sections shown above is arbitrary and for
illustration purposes only. Drawings are not to scale.
If you have questions about linking the trunk line in your MV
controllers, contact technical support.
Procedure
1. Join the sections, following the procedures stated in the starter user
manual.
2. To link the DeviceNet trunk lines lines between separate sections,
connect the linking plug from the right section into the left section
linking receptacle (chetmag). Refer to Figure 4.1. Torque connector
screws to 5 lb.-in. (0.6 Nm).
Connecting DeviceNet
within MV Controller
Line-up