7-2

System Commissioning and Software Installation

1500-IN057C-EN-P – June 2013

When installing a DeviceNet MV controller line-up, use the following

checklist before applying power to the network:


Number of nodes does not exceed 64, with three nodes reserved for

scanner (node 00), PC (node 62), and new device (node 63)

Individual drop lengths do not exceed 20 feet (6 m)

Cumulative drop length does not exceed the desired network baud

rate limit: 128 feet (39 m) at 500 kbps or 256 feet (78 m) at 250 kbps

Total trunk length does not exceed the maximum allowable per the

network baud rate: 246 feet (75 m) at 500 kbps or 492 feet (150 m) at

250 kbps

Verify that all devices are programmed to the same baud rate and

autobaud is disabled

Verify that terminating resistors are in place at the trunk line

terminations and measure for proper resistors (121 ohms, 1/4 W, 1%,

metal film)

Verify that the power supply for the system is 24 Vdc

Total power load and distribution points do not exceed 8 A

The system has one, and only one, earth ground for the V-

There is an earth ground connection

All connections are inspected for loose wires, opens, and shorts

The following general steps, along with references for more information,

are provided to assist with the DeviceNet software installation process.

1. Install the communication card in your personal computer.

2. Load the Windows hardware drivers for the communication card.

3. Load RSNetworx™ for DeviceNet and RSLinx software.

4. Configure the RSLinx driver.

Within the RSWho function, make sure no unrecognized devices

(i.e., ―?‖ symbols) appear for any devices. If an unrecognized device

appears, load the Electronic Data Sheet (EDS) file. See the ―How to

Find Electronic Data Sheets (EDS)‖ in Appendix A.

I M P O R T A N T

I M P O R T A N T

Do not leave the RSWho constantly browsing. Be sure

to close the RSWho screen or disable the Autobrowse.