Rockwell Automation 1500 DeviceNet MV Controllers Installation Instructions User Manual

Page 23

Advertising
background image

DeviceNet Power Supply

6-3

1500-IN057

C-EN-P – June 2013

Connecting Two Power Supplies

When an additional 24 Vdc Class 1 power supply must be installed for

MV controller line-ups, the red trunk conductor between the power

supplies must be broken. Locate a linking connector between sections

and disconnect the red conductor (refer to the following figure).

Ground only ONE of the two power supplies.

Power Supply

Power Supply

Red V+

White CAN_H

Blue CAN_L

Black V- (common)

break

Power Supply

Power Supply

Red V+

White CAN_H

Blue CAN_L

Black V- (common)

break

Figure 6.2 – Connecting Two DeviceNet Power Supplies

MCC line-ups with more than 10 2-Hi sections could exceed the 39

meters (128 feet) cumulative drop limit to support 500 kbps

communications. When the trunk length exceeds this limit, 250 kbps

communications should be specified.