Terminals and wiring, Reliability – Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual

Page 10

Advertising
background image

All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

10

Rockwell Automation Publication 1606-RM030A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

11. Terminals and Wiring

Input Output

Type

screw terminals

screw terminals

Solid wire

0.5-6mm

2

0.5-6mm

2

Stranded wire

0.5-4mm

2

0.5-4mm

2

American Wire Gauge

20-10 AWG

20-10 AWG

Wire stripping length

7mm / 0.275inch

7mm / 0.275inch

Screwdriver

3.5mm slotted or
Pozidrive No 2

3.5mm slotted or
Pozidrive No 2

Recommended tightening torque

0.8Nm, 7lb.in

0.8Nm, 7lb.in

Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:

60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.

b)

Follow national installation codes and regulations!

c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without grounding it to the earth (PE).
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed, but not required.



12. Reliability

AC 400V

AC 480V

Lifetime expectancy

*)

51 000h

55 000h

at 12V, 8A and 40°C

152 000h

147 000h

at 12V, 4A and 40°C

144 000h

156 000h

at 12V, 8A and 25°C

MTBF

**)

SN 29500, IEC 61709

983 000h

967 000h

at 12V, 8A and 40°C

1 799 000h

1 769 000h

at 12V, 8A and 25°C

MTBF

**)

MIL HDBK 217F

484 000h

455 000h

at 12V, 8A and 40°C; Ground Benign GB40

636 000h

600 000h

at 12V, 8A and 25°C; Ground Benign GB25

*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime

expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.

**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a

device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.