Output – Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual

Page 6

Advertising
background image

All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

6

Rockwell Automation Publication 1606-RM030A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

6. Output

Output voltage

nom.

12V

Adjustment range

min.

12-15V

guaranteed

max.

16.0V

at clockwise end position of potentiometer

Factory setting

12.0V

±0.2%, at full load, cold unit

Line regulation

max.

10mV

323-576Vac

Load regulation

max.

100mV

static value, 0A 8A

Ripple and noise voltage

max.

100mVpp

20Hz to 20MHz, 50Ohm

Output capacitance

typ.

5 200μF

Output current

nom.

8A

at 12V, see Fig. 6-1

nom.

6.4A

at

15V,

see

Fig.

6-1

Output power

nom.

96W

Short-circuit current

min.

12A

continuous current, short circuit impedance 100mOhm

max.

15A

continuous current, short circuit impedance 100mOhm

Fig. 6-1 Output voltage vs. output current,

typ.

Output Voltage

0

0

4

8

3

6

15V

9

12

0

1

2

1

6

2

14A

Adjustment

Range

Output Current



Peak current capability (up to several milliseconds)

The power supply can deliver a peak current which is higher than the specified short term current. This helps to start
current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be
discharged and causes a voltage dip on the output. Detailed curves can be found in section 23.1.

Peak current voltage dips

typ.

from 12V to 7V

at 16A for 50ms, resistive load

typ.

from 12V to 7V

at 40A for 2ms, resistive load

typ.

from 12V to 3.7V

at 40A for 5ms, resistive load

Advertising