Efficiency and power losses – Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual

Page 8

Advertising
background image

All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

8

Rockwell Automation Publication 1606-RM030A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

8. Efficiency and Power Losses

AC 400V

AC 480V

Efficiency

typ.

85.4%

85.8%

at 12V, 8A

Average efficiency *)

typ.

84.7%

84.1%

25% at 2A, 25% at 4A, 25% at 6A. 25% at 8A

Power losses

typ.

1.5W

1.6W

at 0A

8.4W

9.1W

at

12V,

4A

typ.

16.4W

15.9W

at

12V,

8A

*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%

of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.


Fig. 8-1

Efficiency vs. output current at 12V,
typ.

Fig. 8-2 Losses vs. output current at 12V,

typ.

Efficiency

1

82

84

86

81

87%

8A

2

4

5

Output Current

3

83

85

400Vac

480Vac

6

7

Power Losses

0

1

2

4

5

8A

0

3

9

15

18W

6

3

12

Output Current

6

7

400Vac

480Vac

Fig. 8-3

Efficiency vs. input voltage at 12V,
8A, typ.

Fig. 8-4 Losses vs. input voltage at 12V, 8A,

typ.

Efficiency

320

360

400

440

480

87%

84.5

85.5

86.5

86.0

85.0

84.0

520

560

Input Voltage Vac

Power Losses

320

360

400

440

480

18W

3

9

15

12

6

o

520

560

Input Voltage Vac

Advertising