All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM030A-EN-P — April 2014

7

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

AC 400V

AC 480V

Hold-up Time

typ.

33ms

58ms

at 12V, 8A, see Fig. 7-1

typ.

63ms

110ms

at 12V, 4A, see Fig. 7-1

Fig. 7-1 Hold-up time vs. input voltage

Fig. 7-2 Shut-down behavior, definitions

0

25

50

75

100ms

320

360

400

440

480Vac

Input Voltage

Hold-up Time at 12Vdc

4A

, t

yp

.

8A,

min

.

8A,

typ

.

4A

, mi

n.

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input
Voltage