Rockwell Automation 1606-XLE96B-2 Power Supply Reference Manual User Manual
Page 11
 
All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM030A-EN-P — April 2014
11
Bulletin 1606 Switched Mode Power Supplies
13. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. The CE Mark indicates conformance with EMC guideline 89/336/EC, 
93/68/EC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EC and 2006/95/EC. A detailed EMC report is 
available on request. 
 
EMC Immunity
Generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
Contact discharge 
Air discharge 
8kV 
15kV 
Criterion A 
Criterion A 
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines 
Output lines 
4kV 
2kV 
Criterion A 
Criterion A 
Surge voltage on input
EN 61000-4-5
L1 L2
2kV
Criterion A
Surge voltage on input
EN 61000-4-5
L1 PE, L2 PE
4kV
Criterion A
Surge voltage on output
EN 61000-4-5
+ - 
+ / - PE 
500V 
500V 
Criterion A 
Criterion A 
Conducted disturbance
EN 61000-4-6
0.15-80MHz
10V
Criterion A
Mains voltage dips
EN 61000-4-11
0% of 380Vac
0% of 480Vac
0Vac, 20ms 
0Vac, 20ms 
Criterion A 
Criterion A 
Mains voltage dips
EN 61000-4-11
40% of 380Vac 
40% of 480Vac
70% of 380Vac 
70% of 480Vac 
200ms 
200ms 
500ms 
500ms 
Criterion C 
Criterion C 
Criterion A 
Criterion A 
Voltage interruptions
EN 61000-4-11
0Vac,
5000ms
Criterion
C
Voltage sags
SEMI F47 0706
80% of 380Vac, load: 12V, 4A 
70% of 380Vac, load: 12V, 4A
50% of 380Vac, load: 12V, 4A
1000ms 
500ms 
200ms 
Criterion A 
Criterion A 
Criterion A 
Voltage sags
SEMI F47 0706
80% of 480Vac, load: 12V, 8A 
70% of 480Vac, load: 12V, 8A
50% of 480Vac, load: 12V, 8A
1000ms 
500ms 
200ms 
Criterion A 
Criterion A 
Criterion A 
Powerful transients
VDE 0160
over entire load range
1550V, 1.3ms
Criterion A
Criteria:
A:
Power supply shows normal operation behavior within the defined limits.
C:
Temporary loss of function is possible. Power supply may shut-down and restart by itself. No damage or hazards for the power supply
will occur.
EMC Emission
Generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22
Class B, input lines
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
fulfilled
Voltage fluctuations, flicker
EN 61000-3-3
fulfilled
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
Switching frequency
Variable between 45kHz and 170kHz depending on load and input voltage