Chapter 1
Introduction, Inspection & Storage

1-5

Enable/Contingency
Coast Stop –
System Reset –
Motor Thermostat –
Communication Port –

24VDC / 115VAC, hard-wired to DC con-
tactor
24VDC / 115VAC, Isolated
24VDC / 115VAC, Isolated
RS–422 for programming terminal

External Inputs:

Drive Ready/Faulted–

N.O. relay contact, open when drive faulted
or de-energized, closed when ready. Con-
tact rating – 1 ADC @ 24 VDC or 0.5A @
120VAC

External Outputs:

Ambient Operating
Temperature
Relative Humidity
Altitude

0

°

to 40

°

C (32

°

– 104

°

F)

5% to 95%, non-condensing
3,300 feet (1,000 meters)

Environmental

Accel/Decel

Preset Speeds
Jog Speeds
“S” Ramp
Motor Operated Pot
(MOP)

0.1 to 6553.5 seconds, independently
programmable.
5 adjustments, programmable
2 adjustments, programmable
Programmable
10 adjustments, programmable

Standard Features

Discrete Adapter
Board;

Digital Inputs (4) –

Digital Outputs (2) –

Analog Inputs (4) –

Analog Outputs (4) –

Power Supply (For
external use) –

24VDC or 120VAC, 10 mA. NOTE: A
separate board and part number is used for
each voltage rating.

Dry relay contacts rated at 0.6A at
125VAC or 2.0A at 30VDC.

0 to +/– 10VDC, differential input imped-
ance – 20K ohms.

–10 to + 10VDC, 1mA minimum output
impedance – 200 ohms.

+10VDC, 4mA maximum, –10VDC,
4mA maximum.

Options

Incremental, dual channel; 12 volts,
500mA, isolated with differential transmit-
ter, 102.5 kHz max. Quadrature : 90

° ±

27

°

@ 25

°

C, Duty Cycle: 50%

±

10% Source/

Sink capable, A–B 845H or equal.

Feedback Devices: Cont.

Encoder –