1+1 redundancy up to 20a, N+1 redundancy, example with 60a – Rockwell Automation 1606-XLSRED40 Power Supply Reference Manual User Manual

Page 16

Advertising
background image

All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise.

16

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

17.4. 1+1 Redundancy up to 20A

1+1 Redundancy up to 20A requires two 20A power supplies and one 1606-XLSRED40 redundancy module.

Fig. 17-1 Wiring diagram, 1+1 Redundancy, 20A output current

L1
L2

PE

L3

20A

Load

Failure

Monitor

I

I

I

I

I

I

L1 L2 L3 PE

+ +

- -

Power

Supply

24V,20A

DC-
OK

L1 L2 L3 PE

+ +

- -

Power

Supply

24V,20A

DC-
OK

1606-
XLSRED40

Redundancy

Module

Output

Input

1

Input

2

+

-

+

-

+

-

Note: Use separate mains systems for each power supply whenever possible.

17.5. N+1 Redundancy, Example with 60A

N+1 Redundancy up to 60A requires four 20A power supplies and two 1606-XLSRED40 redundancy modules.

Fig. 17-2 Wiring diagram, n+1 Redundancy, 60A output current

60A

Load

Failure

Monitor

I

I

I

I

I

I

I

I

I

L1
L2

PE

L3

L1 L2 L3 PE

+ +

- -

Power

Supply

24V,20A

DC-
OK

L1 L2 L3 PE

+ +

- -

Power

Supply

24V,20A

DC-
OK

1606-
XLSRED40

Redundancy

Module

Output

Input

1

Input

2

+

-

+

-

+

-

L1 L2 L3 PE

+ +

- -

Power

Supply

24V,20A

DC-
OK

L1 L2 L3 PE

+ +

- -

Power

Supply

24V,20A

DC-
OK

1606-
XLSRED40

Redundancy

Module

Output

Input

1

Input

2

+

-

+

-

+

-

I

I

I

Note: Use separate mains systems for each power supply whenever possible.