All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

9

Bulletin 1606 Switched Mode Power Supplies

9. EMC

The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment without any restrictions. A detailed EMC report is available on request.

EMC Immunity

According generic standards: EN 61000-6-1 and EN 61000-6-2

Electrostatic discharge

EN 61000-4-2

Contact discharge
Air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

20V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Input lines
Output lines

2kV
2kV

Criterion A
Criterion A

Surge voltage on input
lines

EN 61000-4-5

+

-

+/- Chassis ground

500V
1kV

Criterion A
Criterion A

Surge voltage on output
lines

EN 61000-4-5

+

-

+/- Chassis ground

500V
1kV

Criterion A
Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

20V

Criterion A

Power-frequency magnetic
field *)

EN 61000-4-8

50Hz

30A/m

Criterion A

Criteria:

A: Redundancy module shows normal operation behavior within the defined limits.
Notes:
*) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall

elements, electrodynamic microphones, etc.

EMC Emission

According generic standards: EN 61000-6-3 and EN 61000-6-4

Conducted emission

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

limits for DC power ports according
EN 61000-6-3 fulfilled

*)

Radiated emission

EN 55011, EN 55022

Class B

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

*)

For information only, not mandatory for EN 61000-6-3. Provided, that power sources connected on the inputs fulfill the requirements too.

Switching frequency

The internal auxiliary supply is generated with a boost converter.
The switching frequency is typ. 16kHz.