Bulletin 1606 Switched Mode Power Supplies

19.4. Example: N+1 Redundancy up to 30A

N+1 Redundancy up to 30A requires four 10A power supplies and two 1606-XLERED redundancy modules.

Fig. 19-2

Wiring diagram, n+1 Redundancy, 30A output current

optional

I

I

L

N

PE

I

L N PE

10A

Power Supply

+ +

- -

24V, 10A

L N PE

10A

Power Supply

+ +

- -

24V, 10A

L N PE

10A

Power Supply

+ +

- -

24V, 10A

Failure

Monitor

30A

Load

1606-XLERED

+

-

OUT

+

-

IN 1

+

-

IN 2 IN 1 IN 2

1606-XLERED

+

-

OUT

+

-

IN 1

+

-

IN 2 IN 1 IN 2

L N PE

10A

Power Supply

+ +

- -

24V, 10A

I

optional

Note: Whenever possible, use separate mains systems for each power supply.

19.5. Example: Battery Back-up

A battery back-up with 10A requires one 10A power supply and one 1606-XLERED redundancy module.
Please note:
Set output voltage of power supply to 26.5Vdc minimum to ensure that the load current is delivered from the power
supply and not from the charger (battery). Use a fuse between the battery and the 1606-XLERED module!

Fig. 19-3

Wiring diagram, 10A Battery back-up

optional

L

N

PE

24V Battery

I

Battery

Charger

+

-

Failure

Monitor

10A

Load

L N PE

10A

Power Supply

+ +

- -

24V, 10A

1606-XLERED

+

-

OUT

+

-

IN 1

+

-

IN 2 IN 1 IN 2