All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

2

Rockwell Automation Publication 1606-RM033A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

Redundancy Module

Cost Effective Solution to Build Redundant Systems
Dual Input with Single Output
Alarm Relay-contacts for each Input Path
Two Diodes (Common Cathode)
DC24-48V ± 25% (18-60Vdc) Wide-range Input
Full Power Between -40°C and +60°C
Width only 32mm
Rugged Metal Housing
Large Screw Terminals
Easy Wiring:
Distribution Terminal for Negative Pole Included
3 Year Warranty

Description

The 1606-XLERED is a redundancy module specifically
designed to build 1+1 and N+1 redundant systems.
It is equipped with two input channels which can be
connected to 10A power supplies and one output which
can carry nominal currents up to 20A.

The 1606-XLERED includes a monitoring circuit and
is the perfect solution when the power supply has no
DC-OK function. Two LEDs and two relay contacts indicate
when one of the two DC input voltages is out of range
due to a non-functioning or disconnected power supply.

In addition to the 1606-XLERED is the 1606-XLSRED that
does not include monitoring circuitry. It is the perfect
fit when the power supply itself is already equipped
with a DC-OK signal.

Large screw terminals allow for an easy installation and
a huge international approval package for a variety of
applications makes this unit suitable for nearly every
situation.

Specification Quick Reference

Input voltage DC

24-48V ±25%

Input voltage
range

18–60Vdc

Input current

2x 0–10A

continuous

2x

0–16A for

5

seconds

Output current

0–20A

continuous

20–32A

for

5

seconds

25A at

cont.

overload/

short circuit

Input to output
voltage drop

typ. 0.78V
typ. 0.85V
typ. 0.85V

input: 2x5A
input: 1x10A
input: 2x10A

Power losses

typ. 1.0W

at no load

typ.

8.8W

input:

2x5A

typ.

9.5W

input:

1x10A

typ.

18W

input:

2x10A

Temperature range -40°C to +70°C

operational,

Derating 0.5A/°C

+60 to +70°C

Dimensions

32x124x117mm WxHxD

Catalog Numbers

Redundancy

1606-XLERED 24-48V Standard unit

Module

Accessory 1606-XLB

Wall/panel mount

bracket

Certifications

IND. CONT. EQ.

18WM

LISTED

UL 508

UL 60950-1

Class I Div 2

ATEX

II 3G Ex nAC II T3

Marine

EMC, LVD

Marine RINA

GOST R

C-TICK