All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM033A-EN-P — March 2014

5

Bulletin 1606 Switched Mode Power Supplies

4. Power Losses

DC 24V

Power losses

typ.

8.8W input:

2x5A

typ.

9.5W

input: 1x10A

typ.

18.0W

input: 2x10A

Standby power losses

typ.

1.0W

at no output current

Fig. 4-1

Power losses

Power Losses, typ.

0

0

5

10

20

4

8

12

16

20

24W

25A

15

Output Current

5. Alarm Contacts

Both input voltages are monitored individually. If one input voltage is too low or completely lost, it will be indicated
by an alarm relay contact.

Each input has its own monitoring circuitry and relay contact.

Alarm threshold

nom.

21.5V (±0.5V)

Relay contact opens immediately after
the input voltage falls below this value

Contact ratings

min.

60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A

input: 1x10A

max.

1mA at 5Vdc

input: 2x10A

Isolation voltage

see dielectric strength table in section 14.