Example: decoupling of branches, Use in a tightly sealed enclosure – Rockwell Automation 1606-XLERED Power Supply Reference Manual User Manual

Page 17

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM033A-EN-P — March 2014

17

Bulletin 1606 Switched Mode Power Supplies

19.7. Example: Decoupling of Branches

Buffer energy supplied from a DC UPS or buffer module is not wasted in “power branches.”
Please note:
Set output voltage of the power supply to a level sufficient to prevent the buffer unit or DC UPS from starting
unexpectedly. Take the voltage drop of the 1606-XLERED into account.

Fig. 19-5

Wiring diagram, decoupling of buffered branches

I

I

I

L1
L2

PE

L3

Buffered

Load

e.g.

Controller

optional

Load

e.g. Motor

Buffer

Module

Failure

Monitor

1606-XLERED

+

-

OUT

+

-

IN 1

+

-

IN 2 IN 1 IN 2

L N PE

10A

Power Supply

+ +

- -

24V, 10A

Note: Whenever possible, use separate mains systems for each power supply.

19.8. Use in a Tightly Sealed Enclosure

When the redundancy module is installed in a tightly sealed enclosure, the temperature inside the enclosure will be
higher than outside. The inside temperature defines the ambient temperature for the redundancy module.

Results from such an installation:

Power supply is placed in the middle of the box; no other heat producer is inside the box.

Enclosure:

Rittal Typ IP66 Box PK 9516 100, plastic, 110x180x165mm

Load:

24V, 16A; (=80%) load is placed outside the box

Input:

24Vdc

Temperature inside enclosure:

58.8°C (in the middle of the right side of the power supply with a distance of 2cm)

Temperature outside enclosure: 24.6°C
Temperature rise:

34.2K

Advertising