All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

18

Rockwell Automation Publication 1606-RM033A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

19.9. Mounting Orientations

Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended

output

current.

Curve A2

Max allowed output current (results in approximately half the lifetime expectancy of A1).

Fig. 19-6

Mounting

Orientation A
(Standard
orientation)

Redundancy

Module

INPUT

OUTPUT

Output Current

0

10

20

30

40

60°C

4

12

16

20A

50

A1

8

Ambient Temperature

Fig. 19-7

Mounting

Orientation B
(Upside down)

Redundancy

Module

INPUT

OUTPUT

Output Current

0

10

20

30

40

60°C

4

12

16

20A

50

A1

8

Ambient Temperature

Fig. 19-8

Mounting

Orientation C
(Table-top
mounting)

Output Current

0

10

20

30

40

60°C

4

12

16

20A

50

8

A1

A2

Ambient Temperature

Fig. 19-9

Mounting

Orientation D
(Horizontal cw)

Redundancy

Modul

e

INPUT

OUTPUT

Output Current

0

10

20

30

40

60°C

4

12

16

20A

50

8

A1

A2

Ambient Temperature

Fig. 19-10

Mounting

Orientation E
(Horizontal ccw)

Redundancy

Modul

e

INPUT

OUTPUT

Output Current

0

10

20

30

40

60°C

4

12

16

20A

50

8

A1

A2

Ambient Temperature