2 - installation – standard enclosure, Door opening procedure, Opening the low voltage doors – Rockwell Automation 1512A MV Controllers, 400A One-High Cabinet, Standard and Arc-Resistant Enclosure User Manual
Page 11: Chapter 2, Installation – standard enclosure, Chapter

Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013
3
Chapter
2
Installation – Standard Enclosure
Door Opening Procedure
Opening the Low Voltage Doors
Low voltage doors are identified as LV in
1. To access the low voltage compartment, use a flat-head screwdriver and
turn both of the 1/4-turn fasteners, located on the low voltage door, 90° in
a counterclockwise direction.
2. The door is now released and will swing open.
3. Reverse the procedure to secure the doors.
Figure 3 - Standard Cabinet
Access to the Power Bus on page 7
for the procedure to open the swing-
out low voltage panel behind the low voltage door.
IMPORTANT
For information on the installation site preparation, see Publication
ATTENTION: Use suitable personal protective equipment (PPE) per local codes
or regulations. Failure to do so may result in severe burns, injury or death.
.
.
.
.
Low Voltage Door
Medium Voltage Door