Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 56

56
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Chapter 5 Explicit Messaging
3. Choose the communication type and then set the path and
communication method.
4. Click OK to complete the message setup.
RSLogix5000 Software – Message Setup Using CIP Generic
The following example shows how to set up your message instruction to read or
write to a data table in the power monitor using a CIP Generic message type for
RSLogix5000 software. This setup applies to ControlLogix and CompactLogix
programmable logic controllers. The CIP Generic message type does not support
single element reads or writes. In this example, we are reading the Voltage, Amps,
and Frequency data table from the power monitor.
Communication Type
Path
Method
Ethernet
<Backplane (always 1), Slot of Ethernet Module,
Port (always 2 for Ethernet), power monitor IP
Address>
CIP
Serial communication
<Port, Power Monitor Serial Node Address>
CIP