Appendix A PowerMonitor 1000 Data Tables
Table 23 - Discrete Results Parameters
CSP File No.
N19
CIP Instance
12
Applies to
All models
No. of Elements
6
No. of Words
6
Data Type
Integer
Data Access
Read
Table 24 - Discrete Results
Element
No.
Modbus
Address
Element Name
Range
Description
0
30001
Status Input States
0…3
Indicates the current states of the status input.
Bit 0 = Status 1 activated
Bit 1 = Status 2 activated
Bit 2…15 = Reserved
1
30002
Output Word
0…15
Bit 0 = KYZ relay actuated
Bit 1 = KYZ output forced on
Bit 2 = KYZ output forced off
Bit 3 = External demand pulse timeout
Bit 4 = Terminal Locked
Bit 5…15 = Reserved
2
30003
Reserved
0
Reserved for future use.
3
30004
Reserved
0
Reserved for future use.
4
30005
Reserved
0
Reserved for future use.
5
30006
Reserved
0
Reserved for future use.