Publication 1394-IN024B-EN-P — February 2004

1-14

Commissioning Your 1394 SERCOS Interface System

5. Select Data Rate, Cycle Time, and Optical Power settings.

•

Ensure the Data Rate setting matches DIP switches 2 and 3
(baud rate) as set on the system module, or use the Auto
Detect setting.

•

Set the Cycle Time according to the table below.

•

Ensure the Optical Power setting (high or low) matches DIP
switch 1 as set on the system module.

6. Select Finish. Your new module appears under the I/O

Configuration folder in the explorer window.

7. Repeat steps 1-6 for each Logix module.

Logix SERCOS
Module

1394 SERCOS interface

System Module Series

Data
Rate
Mbit/s

SERCOS Ring
Cycle Time

ms

Number
of Axes

1756-M08SE

(Series A)

C or D

4

0.5

N/A

1.0

up to 4

2.0

up to 8

1756-M08SE

(Series B)

D only

8

0.5

N/A

1.0

up to 8

2.0

1756-M16SE or

1784-PM16SE

C or D

4

0.5

N/A

1.0

up to 4

2.0

up to 8

D only

8

0.5

N/A

1.0

up to 8

2.0

up to 16