Understanding logix/drive fault behavior, System module faults, Understanding logix/drive fault behavior -14 – Rockwell Automation 1394 SERCOS Interface Multi-Axis Motion Control System User Manual

Page 50: System module faults -14

Advertising
background image

Publication 1394-IN024B-EN-P — February 2004

2-14

Troubleshooting Your 1394 SERCOS Interface System

Understanding Logix/Drive
Fault Behavior

This section provides the drive fault actions and indicates whether the
fault action is programmable.

The following drive fault action definitions apply:

System Module Faults

Drive Fault Action

Definition

Shutdown

The drive disables and the contactor enable relay opens. Uncontrolled
stop, motor coasts to a stop.

Disable Drive

The drive is disabled. Uncontrolled Stop, motor coasts to a stop.

Stop Motion

The drive switches internally to velocity mode and sets the command to 0.
Logix configuration for velocity loop Kp/Ki is followed. When zero speed is
reached or stopping time is exceeded, the drive is disabled.
Note: Stopping time and stopping torque are configurable parameters in

RSLogix 5000.

Status Only

Drive continues to operate. Status is provided by System Module Status
LED and SCANport/DPI (if used).

Fault Message
RSLogix
(HIM):

Description:

Drive Fault
Action

RSLogix
Programmable
Fault Action?

DriveOvercurrent

Fault

(Bus Overcurrent)

System module exceeded current rating.

SHUTDOWN

No

DriveOvervoltage

Fault

(Bus Overvoltage)

The DC bus voltage is above limits. If it exceeds (830V dc), a fault is
sensed and the power supply is disabled.

SHUTDOWN

No

DriveUndervoltage

Fault

(Bus Precharge)

The system module pre-charge cycle has failed.

SHUTDOWN

No

DriveUndervoltage

Fault

(Bus Undervoltage)

The DC power bus activates undervoltage limit when the bus drops
to 275V dc or less. It will clear at 300V dc.

SHUTDOWN

No

DriveHardFault

(Can Init)

SCANport hardware initialization fault detected.

SHUTDOWN

No

DriveHardFault

(Contactor Fault)

Three-phase power is either detected when it shouldn’t be or not
detected when it should be.

SHUTDOWN

No

MotFeedbackFault

(Fdbk Watch Dog)

A feedback hardware or software fault detected.

DISABLE

No

GroundShortFault

(Ground Short)

Excessive ground current in the system module was detected.

SHUTDOWN

No

DriveHardFault

(IDMA Load)

Motor feedback hardware initialization fault detected.

SHUTDOWN

No