Connecting program parameters Chapter 1

Special considerations apply when using program parameters within safety

programs.

General rules for connecting parameters for safety programs

The following are general rules when connecting parameters for safety programs.

A safety parameter cannot connect to a standard parameter or controller

scoped tag of standard class; the controller scope must be of class safety.

A safety parameter can source a standard parameter, as shown in the

following image.

Safety Output parameters cannot connect to a standard class InOut

parameter.

Safety local tags can alias safety class controller scope tags.

Safety Public parameters can alias safety class controller scope tags.

Safety program parameters

Rockwell Automation Publication 1756-PM021A-EN-P - October 2014