Program parameter connection rules – Rockwell Automation Logix5000 Program Parameters Programming Manual User Manual
Page 28

Chapter 1 Connecting program parameters
The following information summarizes the program parameter connection rules.
Standard program to standard program connection rules
The following table summarizes the rules for using program parameters to connect
two standard programs.
Tip: The connection rules for programs also apply to Equipment Phases.
Program_A
(Standard)
Program_B
(Standard)
Input
Output
InOut
Public Controller Scope Tag
(Standard Class)
Input
—
Yes
—
Yes
Yes
Output
Yes
—
Yes*
Yes
Yes
InOut
—
Yes*
—
Yes
Yes
Public
Yes
Yes
Yes
—
Alias
Controller Scope Tag
(Standard Class)
Yes
Yes
Yes
Alias
Alias
•
* An InOut parameter can only be connected to an Output parameter if the
InOut parameter is configured as a constant.
•
An Input parameter from Program_A can connect to an Output parameter
of Program_A (wrap around).
•
Parameters of the same type cannot be connected together.
•
Public tags can only bind to controller scope tags using an alias.
Program parameter
connection rules
28
Rockwell Automation Publication 1756-PM021A-EN-P - October 2014