1746-P3 Wiring Considerations
This information describes special wiring considerations for the 1746-P3 power 
supply that are not labeled as revision (REV) B.
ATTENTION
!
Any voltage applied to the 1746-P3 DC NEUT terminal will be 
present at the SLC logic ground and the processor DH-485 port. 
To prevent unwanted potentials across the logic ground of the 
controller and/or damage to the SLC chassis, the DC NEUTRAL 
terminal of the external DC power source must be either 
isolated from the SLC chassis ground or connected to earth 
ground as shown in the following illustration.
IMPORTANT
 SLC 500 series A chassis (1746-A4, 1746-A7, 1746-A10, and 
1746-A13) manufactured before November 1992 have a resistor 
between the logic ground and chassis ground as the drawing on 
the following page illustrates. This resistor could be damaged if 
the wiring recommendation described within the attention box 
above is not followed. See the figure on the following page for 
the location of the resistor. SLC 500 series A chassis (1746-A4, 
1746-A7, 1746-A10, and 1746-A13) with a manufacture date of 
November 1992 or later do not have this resistor. SLC 500 series 
B chassis have a 1 M
Ω
resistor that limits the current between
logic ground and chassis ground.
+24V dc
DC Neut
+24V dc
DC Neut
DH-485
 Port
•
External DC Power Source
Door
1746-P3
Processor
SLC 500 Chassis
SLC Logic Ground
Chassis 
Ground
Earth Ground
Earth
Ground
A jumper wire is 
recommended between 
the DC NEUT and Chassis 
Ground of the external 
power source.