12 Installation Instructions

Publication 1746-IN004B-EN-P - March 2008

5. (Optional) For the 1746-P1, 1746-P2, 1746-P4, 1746-P5, and 1746-P6 power

supplies, use PWR OUT +24V dc and PWR OUT COM terminals to power
24V dc sensors and loads. The terminals on the 1746-P1, 1746-P2, 1746-P5,
and 1746-P6 power supplies provide an isolated, non-fused 200 mA, 24V dc
power supply. The terminals on the 1746-P4 power supply provide an
isolated, non-fused 1A, 24V dc power supply. (The 1746-P3 and 1746-P7
power supplies do not provide for an external power source.)

+24V dc

DC Neut

Not Used

Not Used

Chassis
Ground

DH-485
Port

Door

1746-P3

Processor

SLC 500 Chassis

SLC Logic Ground

Chassis Ground

Resistor

Earth

Ground

PWR OUT +24V dc

PWR OUT COM

PWR OUT +24V dc

PWR OUT COMMON

Catalog Number

1746-P1, 1746-P2, 1746-P5, & 1746-P6

Catalog Number

1746-P4

User Power

User Power