Installation Instructions 13

Publication 1746-IN004B-EN-P - March 2008

SLC 500 Operation with 24V dc User-power Overcurrent
Condition

6. Remove the protective label.

Cat. No.

SLC Operation

Recovery Procedure

1746-P1 series A (made in Japan)

Power supply shutdown, CPU Fault

Reload user program

1746-P1 series A (made in Malaysia-
current production)

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P2 series A, B

Power supply shutdown, CPU Fault

Reload user program

1746-P2 series C

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P4 series A

Power supply shutdown, CPU Fault

Reload user program

1746-P5 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P6 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

ATTENTION

!

For 1746-P1 (made in Malaysia), 1746-P2 series C, 1746-P5 series
A, and 1746-P6 series A power supplies, monitor the 24V dc
user output with a 24V dc input channel to avoid unexpected
operation due to 24V dc user power shutdown.