2. Connect the ground screw of the power supply to the nearest ground or

ground bus. Use a 1.68 mm (#14 AWG) 75

°

Copper wire (Category 1 per

Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1) and keep the leads as short as possible. The 1746-P4 is shown
below.

3. Refer to page 11 for special wiring considerations for the 1746-P3.

4. Connect incoming power. See illustration on page 10.

ATTENTION

!

Turn off incoming power before connecting wires;
failure to do so could cause injury to personnel and/or
equipment.

Use 1.68 mm (#14 AWG) Copper wire. Tighten terminal
screws to 0.8 Nm (7 lb-in).

Chassis Ground

Nearest Ground Bus

Tighten terminal screws to
0.8 Nm (7 lb-in).