Rockwell Automation 1747-PCINT API Software for 1746 I/O User Manual
Page 125
Advertising

OC_SetOutputUpdate Mode
Library of Routines
6–71
Publication 1747-6.5.3 June 1998
Return Value:
Considerations:
Supported in the DOS API library and the Windows NT API library
Example:
HANDLE
Handle;
int
retcode;
retcode = OC_SetOutputUpdateMode( Handle, OUTUPD_NEVER );
/* Must use OC_DemandOutputScan() function to send new output data */
Name:
Value:
Description:
SUCCESS
0
conditional scan was set successfully
ERR_OCACCESS
2
handle
does not have access to the scanner
ERR_OCINIT
5
scanner has not been initialized, see OC_InitScanner
ERR_OCPARAM
8
parameter contains invalid value
Advertising
This manual is related to the following products: