ControlNet Communication Interface Card

Publication 1784-5.33 – September 1997

Running the KTCX15 Card Installation Check Utility in DOS or WIN95

To make sure you have installed the card properly, run the installation check
utility. Follow these steps:

1. Place the utility disk in drive A of the host computer.

If you are running the utility software from another drive, use the appropriate
drive letter.

If you are using WIN95:

a.

From the Windows 95 Start Menu, select RUN.

The Run dialog box appears.

b.

Type the path and command to run the utility.

a:\ktcinst 8

(where

8

is the network address you’ve selected)

c.

Click OK.

If you are using DOS or a DOS window in WIN95:

a.

At the DOS prompt, type:

a:\ktcinst

You see a screen/window similar to this one:

1784–KTCX15 Card Installation Check Utility

Version 1.xx DD–MMM–YY

Copyright 1997 Allen–Bradley Company, Inc.

Usage: KTCINST NetworkAddress [IOaddress]

NetworkAddress= KTCX Network Address, in hex
IOaddress = KTCX I/O base address (Default 220), in hex

In order to run the KTCX installation utility, you must specify the
network address and the I/O address, if other than 220.

For a network address of 3 and I/O address of 260, type the following:

KTCINST 3 260

For a network address of 2 and I/O address of 220, (default) type the
following:

KTCINST 2

c:\

ControlNet Communication Interface Card

19

Publication 1784-5.33 – September 1997

2. Type:

a:\ktcinst 8

(where

8

is the network address you’ve selected)

You see:

Warning.. Make sure that the card is not connected to a network. Press any key.

3. Press any key.

You see a similar message:

Succeeded Make sure that the card is not connected to a network.

Succeeded Hard resetting KTCX.

4. Recheck the I/O address if hard resetting fails.

Succeeded I/O Address: 220, Dual Port Address: D000:0000

Are these your intended address settings? [y/n]

5. Press

Y

for yes or

N

for no.

You see a similar message:

Boot code version: 1.3 8/20/96, Serial #: 20 (14)

Main code version: 99.65 4/29/97

Succeeded Testing dual-port interface.

If this test fails, contact your local Rockwell Automation sales representative
or distributor, or Rockwell Automation Technical Support at (440) 646-6800.

Waiting.. Soft resetting KTCX as network address 8. Press any key.

The utility initializes the network media access controller.

6. Press any key.

You see a similar message:

Succeeded Soft resetting KTCX as network address 8.

If this test fails, make certain that you are not connected to a network.
Contact your local Rockwell Automation sales representative or distributor,
or Rockwell Automation Technical Support at (440) 646-6800.

Waiting.. Setting KTCX to online. Press any key.

The utility tests the card’s ability to connect to the network.