18 Compact 32-point Solid-state 24V dc Source Output Module

Publication 1769-IN080A-EN-P - August 2006

Program State Word

Word 1, the program state word, selects the hold
last state or user-defined safe state condition for
each individual output on a system transition
from Run to Program.

Program Value Word

The program value word, word 2, is used to
program the user-defined safe state value (0=Off,
1=On). Each output is individually configurable
for on or off.

Fault State Word

Word 3, the fault state word, selects the hold last
state or user-defined safe state condition for each
individual output on a system transition from Run
to Fault.

Fault Value Word

The fault value word, word 4, is used to program
the fault state value (0=Off, 1=On). Each output
is individually configurable for on or off.

9

Fault Value for Output Array Word 1

10

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

11

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

12

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

13

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

14

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

15

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Configuration File

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Condition Bit

Setting

User-defined safe state

0

Hold last state

1

Value

Bit Setting

Off

0

On

1

Condition Bit

Setting

User-defined safe state

0

Hold last state

1

Value

Bit Setting

Off

0

On

1