22 Compact 32-point Solid-state 24V dc Source Output Module

Publication 1769-IN080A-EN-P - August 2006

(1)

Typical Loading Resistor - To limit the effects of leakage current through solid state outputs, a loading resistor can be
connected in parallel with your load. Use a 56 k ohm, 1/4 W resistor for this module’s outputs, 24V dc operation.

(2)

Recommended Surge Suppression - Use a 1N4004 diode reverse-wired across the load for transistor outputs switching 24V
dc inductive loads. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication 1770-4.1.

(3)

Sourcing output - source describes the current flow between the I/O module and the field device. Sourcing output circuits
source current to sinking field devices. Field devices connected to the negative side (DC Common) of the field power supply
are sinking field devices. Europe: dc sinking input and sourcing output module circuits are the commonly used options.

Environmental Specifications

Attribute

Value

Storage temperature

-40…85 °C (-40…185°F)

Operating temperature

0…60 °C (32…140 °F)

Operating humidity

5…95% noncondensing

Operating altitude

2000 m (6561 ft)

Vibration, operating

10…500 Hz, 5 g, 0.030 in. max peak-to-peak

Shock, operating

30 g panel mounted (20 g DIN-rail mounted)

Shock, nonoperating

40 g panel mounted (30 g DIN-rail mounted)

Radiated and conducted emissions

EN50081-2 Class A

Electrical /EMC

The module has passed testing at the following levels

ESD immunity (IEC61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated immunity (IEC61000-4-3)

10V/m, 80…1000 MHz, 80% amplitude

Fast transient burst (IEC61000-4-4)

2 kV, 5 kHz

Surge immunity (IEC61000-4-4)

2 kV common mode, 1 kV differential mode

Conducted immunity
(IEC61000-4-6)

10V, 0.15…80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30…1000 MHz.

Certifications

Certification

Value

Agency certification

(1)

• C-UL certified (under CSA C22.2 No. 142)

• UL 508 listed

• CE compliant for all applicable directives

Hazardous environment class

Class I, Division 2, Hazardous Location, Groups A, B, C, D

(UL 1604, C-UL under CSA C22.2 No. 213)

(1)

See the Product Certification link at http://www.ab.com for Declarations of Conformity, certificates, and other certification