Refer to the following table for baud rate specifications.
The module produces 1 byte for every 8 inputs. Similarly, the module
consumes 1 byte for every 8 outputs.
Remember, though, when configuring your CompactBlock I/O application,
these values are entered as bytes received (R
x
) and bytes transmitted (T
x
) by
the scanner.
For example, a Base Input module produces 2 bytes and consumes 0 bytes. In
such a case, the scanner connected to the Base Input module will receive (R
x
)
2 bytes and transmit (T
x
) 0 bytes.
Baud Rate
Cable Length
Copper Cable*
9.6KBPS
1000m
19.2KBPS
1000m
45.45KBPS
1000m
93.75KBPS
1000m
187.5KBPS
1000m
500KBPS
400m
1.5MBPS
200m
3MBPS
100m
6MBPS
100m
12MBPS
100m
*Specified in PROFIBUS
Standard as 22AWG shielded
twisted pair cable.
IMPORTANT
When installing an expansion module, refer to the table
below to see how many bytes are produced and
consumed by the modules.