North american hazardous location approval – Rockwell Automation 1791P-XXXX CompactBlock Distributed I/O on PROFIBUS DP Series D I.I. User Manual
Page 29
 
CompactBlock Distributed I/O on PROFIBUS DP Series D 29
Publication
1791P-IN002B-EN-P - October 2003
North American Hazardous Location Approval
The following information applies when
operating this equipment in hazardous
locations:
Informations sur l’utilisation de cet équipement en
environnements dangereux :
Products marked “CL I, DIV 2, GP A, B, C, D” 
are suitable for use in Class I Division 2 Groups 
A, B, C, D, Hazardous Locations and 
nonhazardous locations only. Each product is 
supplied with markings on the rating nameplate 
indicating the hazardous location temperature 
code. When combining products within a system, 
the most adverse temperature code (lowest “T” 
number) may be used to help determine the 
overall temperature code of the system. 
Combinations of equipment in your system are 
subject to investigation by the local Authority 
Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu’à une utilisation en environnements de 
Classe I Division 2 Groupes A, B, C, D dangereux et non 
dangereux. Chaque produit est livré avec des marquages 
sur sa plaque d’identification qui indiquent le code de 
température pour les environnements dangereux. 
Lorsque plusieurs produits sont combinés dans un 
système, le code de température le plus défavorable 
(code de température le plus faible) peut être utilisé pour 
déterminer le code de température global du système. 
Les combinaisons d’équipements dans le système sont 
sujettes à inspection par les autorités locales qualifiées 
au moment de l’installation.
The following information applies when
operating this equipment in hazardous
locations:
Informations sur l’utilisation de cet équipement en
environnements dangereux :
WARNING
EXPLOSION HAZARD
• Do not disconnect
equipment unless power 
has been removed or the 
area is known to be 
nonhazardous. 
• Do not disconnect
connections to this 
equipment unless power 
has been removed or the 
area is known to be 
nonhazardous. Secure any 
external connections that 
mate to this equipment by 
using screws, sliding 
latches, threaded 
connectors, or other 
means provided with this 
product.
• Substitution of
components may impair 
suitability for Class I, 
Division 2.
• If this product contains
batteries, they must only 
be changed in an area 
known to be 
nonhazardous.
AVERTISSEMENT
RISQUE D’EXPLOSION
• Couper le courant ou
s’assurer que 
l’environnement est classé 
non dangereux avant de 
débrancher l'équipement.
• Couper le courant ou
s'assurer que 
l’environnement est classé 
non dangereux avant de 
débrancher les 
connecteurs. Fixer tous les 
connecteurs externes reliés 
à cet équipement à l'aide de 
vis, loquets coulissants, 
connecteurs filetés ou 
autres moyens fournis avec 
ce produit.
• La substitution de
composants peut rendre cet 
équipement inadapté à une 
utilisation en 
environnement de Classe I, 
Division 2.
• S’assurer que
l’environnement est classé 
non dangereux avant de 
changer les piles.