Mount the block(s), Base module mounting – Rockwell Automation 1791P-XXXX CompactBlock Distributed I/O on PROFIBUS DP Series D I.I. User Manual
Page 6

6 CompactBlock Distributed I/O on PROFIBUS DP Series D
Publication
1791P-IN002B-EN-P - October 2003
The switches are read at module power up only.
Mount the Block(s)
The base and expansion modules mount to a panel or DIN rail, which must
be grounded before installing the module(s).
Base Module Mounting
You can install the CompactBlock base module on a panel or DIN rail.
Address
DIP Switches
100’s
Rotary Switches
Position 1
Position 2
10’s
1’s
0-99
0
0
0-9
0-9
100-125
1
0
0-2
0-5
WARNING
When used in a Class I, Division 2, hazardous
location, this equipment must be mounted in a suitable
enclosure with proper wiring method that complies
with the governing electrical codes.
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
2
ON
10
’s
1’
s
Rotary Switches
(00-99)
Example: Node
Address is set at 26
43112
DIP Switches
(100-125)
View when looking into module.
100’s