North American Hazardous Location Approval

The following module is North American Hazardous Location approved:

1794-ID2 Series B

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet
équipement en environnements
dangereux:

Products marked “CL I, DIV 2, GP A, B, C, D” are suitable
for use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product
is supplied with markings on the rating nameplate
indicating the hazardous location temperature code.
When combining products within a system, the most
adverse temperature code (lowest “T” number) may be
used to help determine the overall temperature code of
the system. Combinations of equipment in your system are
subject to investigation by the local Authority Having
Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux et
non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui
indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code de
température le plus défavorable (code de température
le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les
combinaisons d'équipements dans le système sont
sujettes à inspection par les autorités locales
qualifiées au moment de l'installation.

WARNING: EXPLOSION HAZARD

Do not disconnect equipment
unless power has been
removed or the area is known
to be nonhazardous.

Do not disconnect connections
to this equipment unless
power has been removed or
the area is known to be
nonhazardous. Secure any
external connections that mate
to this equipment by using
screws, sliding latches,
threaded connectors, or other
means provided with this
product.

Substitution of components
may impair suitability for Class
I, Division 2.

If this product contains
batteries, they must only be
changed in an area known to
be nonhazardous.

WARNING: RISQUE
D’EXPLOSION

Couper le courant ou
s’assurer que
l’environnement est
classé non dangereux
avant de débrancher
l'équipement.

Couper le courant ou
s'assurer que
l’environnement est
classé non dangereux
avant de débrancher les
connecteurs. Fixer tous
les connecteurs externes
reliés à cet équipement à
l'aide de vis, loquets
coulissants, connecteurs
filetés ou autres moyens
fournis avec ce produit.

La substitution de
composants peut rendre
cet équipement inadapté
à une utilisation en
environnement de Classe
I, Division 2.

S’assurer que
l’environnement est
classé non dangereux
avant de changer les
piles.